The PAMIX EIB Bus Cable F/UTP LSZH is designed for EIB bus systems used in building control systems. It is used for data transmission carrying data in lighting systems KNX, heating systems, air conditioning, and other systems used in building management and control.
General Construction & Design
-
Conductor: 1/0.8mm, 20 AWG annealed solid bar copper.
-
Pairs: 1 or 2 Twisted Pairs cable wires.
-
Insulation: FR-LSZH Insulation, OD: 1.45 ± 0.05mm.
-
Drain Wire: Solid TC drain wire 0.4mm.
-
Screening: 100% coverage overall screening using Aluminum foiling/Mylar tape.
-
Outer Sheath: FR LSZH outer sheath compound in Green color (RAL 6017).
-
Color Code: Red, Black, White, Yellow.
-
Dimensions & Physical Characteristics: Cable OD is 5.5mm ± 0.3mm for 1 Pair Cable and 6.5mm ± 0.3mm for 2 pair cable. Bend radius is 10 X cable diameter. Weight is 37.4Kg / km for 1 pair cable and 59.4Kg / km for 2 pair cable.
-
Outer Sheath Marking: PAMIX EIB BUS Cable X 2 X 0.8mm FUTP FR-LSZH .
Electrical Performance
-
Characteristic Impedance: 100Ω
-
Nominal Conductor Resistance: 38.5 Ω/km
-
Maximum Unbalance Resistance: 2%
-
Mutual Capacitance: Core to core $\le 100$ nF/km
-
Dielectric Strength: 2.5KV for 5 min
-
Insulation Resistance: 200M Ohm.km
Environmental & Standards Compliance
-
Temperature Range: Operating temperature: -20°C to +70°C; Installation temperature: 0°C to +60°C.
-
RoHS & CE: Meets RoHS requirements; CE Compliant (LVD 2014/35/EU, CPR 305/2011).
-
CPR Classification: Eca (EN50575:2014+A1:2016).
-
Smoke Density: IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2.
-
Zero Halogen / Corrosive Gases: IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2.
-
Flame Propagation: IEC 60332-1/-2, EN 60332-1-2, VDE 0482-332-1-2.
-
EMC: Shielded.
Ordering Information
-
Article Number 1501011: PAMIX EIB BUS Cable 1 x 2 x 0.8 FR/LSZH
-
Article Number 1501012: PAMIX EIB BUS Cable 2 x 2 x 0.8 FR/LSZH